Podatność CVE-2017-14469


Publikacja: 2018-04-05   Modyfikacja: 2018-04-06

Opis:
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Code: 0028 Fault Type: Non-User Description: Values 0x01 and 0x02 are invalid values for the user fault routine. By writing directly to the file it is possible to set these values. When this is done and the device is moved into a run state, a fault is triggered. NOTE: This is not possible through RSLogix.

Typ:

CWE-noinfo

CVSS2 => (AV:N/AC:L/Au:N/C:P/I:P/A:P)

Ogólna skala CVSS
Znaczenie
Łatwość wykorzystania
7.5/10
6.4/10
10/10
Wymagany dostęp
Złożoność ataku
Autoryzacja
Zdalny
Niska
Nie wymagana
Wpływ na poufność
Wpływ na integralność
Wpływ na dostępność
Częściowy
Częściowy
Częściowy
Affected software
Rockwellautomation -> Micrologix 1400 b firmware 

 Referencje:
https://www.talosintelligence.com/vulnerability_reports/TALOS-2017-0443