Podatność CVE-2018-11691


Publikacja: 2019-05-14

Opis:
Emerson DeltaV Smart Switch Command Center application, available in versions 11.3.x and 12.3.1, was unable to change the DeltaV Smart Switches? management password upon commissioning. Emerson released patches for DeltaV workstations to address this issue, and the patches can be downloaded from Emerson?s Guardian Support Portal. Please refer to the DeltaV Security Notification DSN19003 (KBA NK-1900-0808) for more information about this issue. DeltaV versions 13.3 and higher use the Network Device Command Center application to manage DeltaV Smart Switches, and this newer application is not impacted by this issue. After patching the Smart Switch Command Center, users are required to either commission the DeltaV Smart Switches or change password using the tool.

Typ:

CWE-798

CVSS2 => (AV:N/AC:L/Au:N/C:C/I:C/A:C)

Ogólna skala CVSS
Znaczenie
Łatwość wykorzystania
10/10
10/10
10/10
Wymagany dostęp
Złożoność ataku
Autoryzacja
Zdalny
Niska
Nie wymagana
Wpływ na poufność
Wpływ na integralność
Wpływ na dostępność
Pełny
Pełny
Pełny
Affected software
Emerson -> Ve6046 firmware 

 Referencje:
http://www.emerson.com/documents/automation/deltav-smart-switches-en-179014.pdf
http://www.securityfocus.com/bid/109110
https://www.us-cert.gov/ics/advisories/icsa-19-190-01