RSS   Vulnerabilities for 'Clearscada'   RSS

2022-02-09
 
CVE-2022-24318

CWE-326
 

 
A CWE-326: Inadequate Encryption Strength vulnerability exists that could cause non-encrypted communication with the server when outdated versions of the ViewX client are used. Affected Product: ClearSCADA (All Versions), EcoStruxure Geo SCADA Expert 2019 (All Versions), EcoStruxure Geo SCADA Expert 2020 (All Versions)

 
 
CVE-2022-24319

CWE-295
 

 
A CWE-295: Improper Certificate Validation vulnerability exists that could allow a Man-in-theMiddle attack when communications between the client and Geo SCADA web server are intercepted. Affected Product: ClearSCADA (All Versions), EcoStruxure Geo SCADA Expert 2019 (All Versions), EcoStruxure Geo SCADA Expert 2020 (All Versions)

 
 
CVE-2022-24320

CWE-295
 

 
A CWE-295: Improper Certificate Validation vulnerability exists that could allow a Man-in-theMiddle attack when communications between the client and Geo SCADA database server are intercepted. Affected Product: ClearSCADA (All Versions), EcoStruxure Geo SCADA Expert 2019 (All Versions), EcoStruxure Geo SCADA Expert 2020 (All Versions)

 
 
CVE-2022-24321

CWE-754
 

 
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause Denial of Service against the Geo SCADA server when receiving a malformed HTTP request. Affected Product: ClearSCADA (All Versions), EcoStruxure Geo SCADA Expert 2019 (All Versions), EcoStruxure Geo SCADA Expert 2020 (All Versions)

 
2020-01-06
 
CVE-2019-6854

CWE-287
 

 
A CWE-264 Permissions, Privileges, and Access Controls vulnerability exists in a folder within EcoStruxure Geo SCADA Expert (ClearSCADA) -with initial releases before 1 January 2019- which could cause a low privilege user to delete or modify database, setting or certificate files. Those users must have access to the file system of that operating system to exploit this vulnerability. Affected versions in current support includes ClearSCADA 2017 R3, ClearSCADA 2017 R2, and ClearSCADA 2017.

 
2018-05-14
 
CVE-2017-6021

CWE-20
 

 
In Schneider Electric ClearSCADA 2014 R1 (build 75.5210) and prior, 2014 R1.1 (build 75.5387) and prior, 2015 R1 (build 76.5648) and prior, and 2015 R2 (build 77.5882) and prior, an attacker with network access to the ClearSCADA server can send specially crafted sequences of commands and data packets to the ClearSCADA server that can cause the ClearSCADA server process and ClearSCADA communications driver processes to terminate. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

 
2017-09-25
 
CVE-2017-9962

CWE-119
 

 
Schneider Electric's ClearSCADA versions released prior to August 2017 are susceptible to a memory allocation vulnerability, whereby malformed requests can be sent to ClearSCADA client applications to cause unexpected behavior. Client applications affected include ViewX and the Server Icon.

 
2014-09-18
 
CVE-2014-5413

CWE-310
 

 
Schneider Electric StruxureWare SCADA Expert ClearSCADA 2010 R3 through 2014 R1 uses the MD5 algorithm for an X.509 certificate, which makes it easier for remote attackers to spoof servers via a cryptographic attack against this algorithm.

 
 
CVE-2014-5412

CWE-264
 

 
Schneider Electric StruxureWare SCADA Expert ClearSCADA 2010 R3 through 2014 R1 allows remote attackers to read database records by leveraging access to the guest account.

 
 
CVE-2014-5411

CWE-79
 

 
Multiple cross-site scripting (XSS) vulnerabilities in Schneider Electric StruxureWare SCADA Expert ClearSCADA 2010 R3 through 2014 R1 allow remote authenticated users to inject arbitrary web script or HTML via unspecified vectors.

 


Copyright 2024, cxsecurity.com

 

Back to Top