RSS   Vulnerabilities for 'Clearscada'   RSS

2018-05-14
 
CVE-2017-6021

CWE-20
 

 
In Schneider Electric ClearSCADA 2014 R1 (build 75.5210) and prior, 2014 R1.1 (build 75.5387) and prior, 2015 R1 (build 76.5648) and prior, and 2015 R2 (build 77.5882) and prior, an attacker with network access to the ClearSCADA server can send specially crafted sequences of commands and data packets to the ClearSCADA server that can cause the ClearSCADA server process and ClearSCADA communications driver processes to terminate. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

 
2017-09-25
 
CVE-2017-9962

CWE-119
 

 
Schneider Electric's ClearSCADA versions released prior to August 2017 are susceptible to a memory allocation vulnerability, whereby malformed requests can be sent to ClearSCADA client applications to cause unexpected behavior. Client applications affected include ViewX and the Server Icon.

 
2014-09-18
 
CVE-2014-5413

CWE-310
 

 
Schneider Electric StruxureWare SCADA Expert ClearSCADA 2010 R3 through 2014 R1 uses the MD5 algorithm for an X.509 certificate, which makes it easier for remote attackers to spoof servers via a cryptographic attack against this algorithm.

 
 
CVE-2014-5412

CWE-264
 

 
Schneider Electric StruxureWare SCADA Expert ClearSCADA 2010 R3 through 2014 R1 allows remote attackers to read database records by leveraging access to the guest account.

 
 
CVE-2014-5411

CWE-79
 

 
Multiple cross-site scripting (XSS) vulnerabilities in Schneider Electric StruxureWare SCADA Expert ClearSCADA 2010 R3 through 2014 R1 allow remote authenticated users to inject arbitrary web script or HTML via unspecified vectors.

 
2014-03-14
 
CVE-2014-0779

CWE-119
 

 
The PLC driver in ServerMain.exe in the Kepware KepServerEX 4 component in Schneider Electric StruxureWare SCADA Expert ClearSCADA 2010 R2 build 71.4165, 2010 R2.1 build 71.4325, 2010 R3 build 72.4560, 2010 R3.1 build 72.4644, 2013 R1 build 73.4729, 2013 R1.1 build 73.4832, 2013 R1.1a build 73.4903, 2013 R1.2 build 73.4955, and 2013 R2 build 74.5094 allows remote attackers to cause a denial of service (application crash) via a crafted OPF file (aka project file).

 
2014-01-15
 
CVE-2013-6142

CWE-399
 

 
DNP3Driver.exe in the DNP3 driver in Schneider Electric ClearSCADA 2010 R2 through 2010 R3.1 and SCADA Expert ClearSCADA 2013 R1 through 2013 R1.2 allows remote attackers to cause a denial of service (resource consumption) via IP packets containing errors that trigger event-journal messages.

 
2011-08-16
 
CVE-2011-3144

CWE-79
 

 
Cross-site scripting (XSS) vulnerability in Control Microsystems ClearSCADA 2005, 2007, and 2009 before R2.3 and R1.4, as used in SCX before 67 R4.5 and 68 R3.9, allows remote attackers to inject arbitrary web script or HTML via unspecified vectors.

 
 
CVE-2011-3143

CWE-399
 

 
Use-after-free vulnerability in Control Microsystems ClearSCADA 2005, 2007, and 2009 before R2.3 and R1.4, as used in SCX before 67 R4.5 and 68 R3.9, allows remote attackers to cause a denial of service (crash) and possibly execute arbitrary code via unspecified long strings that trigger heap memory corruption.

 