| |
Vulnerabilities for 'Simatic wincc runtime professional'
CWE-428
|
A vulnerability has been identified in SIMATIC Automation Tool (All versions), SIMATIC NET PC software (All versions V16 < V16 Upd3), SIMATIC PCS 7 (All versions), SIMATIC PCS neo (All versions), SIMATIC ProSave (All versions), SIMATIC S7-1500 Software Controller (All versions), SIMATIC STEP 7 (All versions < V5.6 SP2 HF3), SIMATIC STEP 7 (TIA Portal) V13 (All versions), SIMATIC STEP 7 (TIA Portal) V14 (All versions), SIMATIC STEP 7 (TIA Portal) V15 (All versions), SIMATIC STEP 7 (TIA Portal) V16 (All versions), SIMATIC WinCC OA V3.16 (All versions < P018), SIMATIC WinCC OA V3.17 (All versions < P003), SIMATIC WinCC Runtime Advanced (All versions), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions), SIMATIC WinCC Runtime Professional V15 (All versions), SIMATIC WinCC Runtime Professional V16 (All versions), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 14), SIMATIC WinCC V7.5 (All versions < V7.5 SP1 Update 3), SINAMICS STARTER commissioning tool (All versions), SINAMICS Startdrive (All versions), SINEC NMS (All versions), SINEMA Server (All versions), SINUMERIK ONE virtual (All versions), SINUMERIK Operate (All versions). A component within the affected application regularly calls a helper binary with SYSTEM privileges while the call path is not quoted. |
|
CWE-20
|
A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC (TIA Portal) V13 (All versions), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1 Upd 9), SIMATIC WinCC (TIA Portal) V15 (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). An authenticatd attacker with network access to the DCOM interface could execute arbitrary commands with SYSTEM privileges. The vulnerability could be exploited by an attacker with network access to the affected system. Successful exploitation requires authentication with a low-privileged user account and no user interaction. An attacker could use the vulnerability to compromise confidentiality and integrity and availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known. |
|
CWE-20
|
A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC (TIA Portal) V13 (All versions), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1 Upd 9), SIMATIC WinCC (TIA Portal) V15 (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). An attacker with local access to the project file could cause a Denial-of-Service condition on the affected product while the project file is loaded. Successful exploitation requires access to the project file. An attacker could use the vulnerability to compromise availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known. |
|
CWE-20
|
A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC (TIA Portal) V13 (All versions), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1 Upd 9), SIMATIC WinCC (TIA Portal) V15 (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). An attacker with access to the project file could run arbitrary system commands with the privileges of the local database server. The vulnerability could be exploited by an attacker with access to the project file. The vulnerability does impact the confidentiality, integrity, and availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known. |
|
CWE-20
|
A vulnerability has been identified in OpenPCS 7 V7.1 and earlier (All versions), OpenPCS 7 V8.0 (All versions), OpenPCS 7 V8.1 (All versions < V8.1 Upd5), OpenPCS 7 V8.2 (All versions < V8.2 SP1), OpenPCS 7 V9.0 (All versions < V9.0 Upd1), SIMATIC BATCH V7.1 and earlier (All versions), SIMATIC BATCH V8.0 (All versions < SIMATIC BATCH V8.0 SP1 Upd21), SIMATIC BATCH V8.1 (All versions < SIMATIC BATCH V8.1 SP1 Upd16), SIMATIC BATCH V8.2 (All versions < V8.2 SP1), SIMATIC BATCH V9.0 (All versions < V9.0 SP1), SIMATIC NET PC-Software (All versions), SIMATIC PCS 7 V7.1 and earlier (All versions), SIMATIC PCS 7 V8.0 (All versions), SIMATIC PCS 7 V8.1 (All versions), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP1), SIMATIC Route Control V7.1 and earlier (All versions), SIMATIC Route Control V8.0 (All versions), SIMATIC Route Control V8.1 (All versions), SIMATIC Route Control V8.2 (All versions < V8.2 SP1), SIMATIC Route Control V9.0 (All versions < V9.0 Upd1), SIMATIC WinCC Runtime Professional V13 (All versions < V13 SP2 Upd2), SIMATIC WinCC Runtime Professional V14 (All versions < V14 SP1 Upd5), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < WinCC 7.3 Upd 16), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd4). Specially crafted messages sent to the RPC service of the affected products could cause a Denial-of-Service condition on the remote and local communication functionality of the affected products. A reboot of the system is required to recover the remote and local communication functionality. |
|
|
Copyright 2024, cxsecurity.com
|
|
|