RSS   Podatności dla 'Micrologix 1400 b firmware'   RSS

2019-04-25
 
CVE-2019-10955

CWE-601
 

 
In Rockwell Automation MicroLogix 1400 Controllers Series A, All Versions Series B, v15.002 and earlier, MicroLogix 1100 Controllers v14.00 and earlier, CompactLogix 5370 L1 controllers v30.014 and earlier, CompactLogix 5370 L2 controllers v30.014 and earlier, CompactLogix 5370 L3 controllers (includes CompactLogix GuardLogix controllers) v30.014 and earlier, an open redirect vulnerability could allow a remote unauthenticated attacker to input a malicious link to redirect users to a malicious site that could run or download arbitrary malware on the user?s machine.

 
2018-06-04
 
CVE-2017-12092

CWE-200
 

 
An exploitable file write vulnerability exists in the memory module functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a file write resulting in a new program being written to the memory module. An attacker can send an unauthenticated packet to trigger this vulnerability.

 
2018-04-05
 
CVE-2017-14473

CWE-noinfo
 

 
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: Any Description: Reads the encoded ladder logic from its data file and print it out in HEX.

 
 
CVE-2017-14472

CWE-noinfo
 

 
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: Any Description: Requests a specific set of bytes from an undocumented data file and returns the ASCII version of the master password.

 
 
CVE-2017-14471

CWE-noinfo
 

 
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Codes: 0023, 002e, and 0037 Fault Type: Recoverable Description: The STI, EII, and HSC function files contain bits signifying whether or not a fault has occurred. Additionally there is a bit signaling the module to auto start. When these bits are set for any of the three modules and the device is moved into a run state, a fault is triggered.

 
 
CVE-2017-14470

CWE-noinfo
 

 
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG or RUN Description: The value 0xffffffff is considered NaN for the Float data type. When a float is set to this value and used in the PLC, a fault is triggered. NOTE: This is not possible through RSLogix.

 
 
CVE-2017-14469

CWE-noinfo
 

 
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Code: 0028 Fault Type: Non-User Description: Values 0x01 and 0x02 are invalid values for the user fault routine. By writing directly to the file it is possible to set these values. When this is done and the device is moved into a run state, a fault is triggered. NOTE: This is not possible through RSLogix.

 
 
CVE-2017-14468

CWE-noinfo
 

 
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Description: This ability is leveraged in a larger exploit to flash custom firmware.

 
 
CVE-2017-14467

CWE-noinfo
 

 
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE Description: Live rung edits are able to be made by an unauthenticated user allowing for addition, deletion, or modification of existing ladder logic. Additionally, faults and cpu state modification can be triggered if specific ladder logic is used.

 
 
CVE-2017-14466

CWE-noinfo
 

 
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Description: The filetype 0x03 allows users write access, allowing the ability to overwrite the Master Password value stored in the file.

 


Copyright 2024, cxsecurity.com

 

Back to Top