Vulnerability CVE-2011-3322


Published: 2011-09-15   Modified: 2012-02-13

Description:
Core Server HMI Service (Coreservice.exe) in Scadatec Limited Procyon SCADA 1.06, and other versions before 1.14, allows remote attackers to cause a denial of service (crash) and possibly execute arbitrary code via a long password to the Telnet (TCP/23) port, which triggers an out-of-bounds read or write, leading to a stack-based buffer overflow.

See advisories in our WLB2 database:
Topic
Author
Date
High
Procyon Core Server HMI <= v1.13 Coreservice.exe Stack Buffer Overflow
metasploit
17.09.2011

Type:

CWE-119

(Improper Restriction of Operations within the Bounds of a Memory Buffer)

CVSS2 => (AV:N/AC:L/Au:N/C:C/I:C/A:C)

CVSS Base Score
Impact Subscore
Exploitability Subscore
10/10
10/10
10/10
Exploit range
Attack complexity
Authentication
Remote
Low
No required
Confidentiality impact
Integrity impact
Availability impact
Complete
Complete
Complete
Affected software
Scadatec -> Procyon scada 

 References:
http://www.uscert.gov/control_systems/pdf/ICSA-11-216-01.pdf
http://xforce.iss.net/xforce/xfdb/69632
http://www.stratsec.net/Research/Advisories/Procyon-Core-Server-HMI-Remote-Stack-Overflow
http://www.securityfocus.com/bid/49480
http://www.exploit-db.com/exploits/17827
http://secunia.com/advisories/45866
http://osvdb.org/75371

Copyright 2024, cxsecurity.com

 