Vulnerability CVE-2017-14471


Published: 2018-04-05

Description:
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Codes: 0023, 002e, and 0037 Fault Type: Recoverable Description: The STI, EII, and HSC function files contain bits signifying whether or not a fault has occurred. Additionally there is a bit signaling the module to auto start. When these bits are set for any of the three modules and the device is moved into a run state, a fault is triggered.

Type:

CWE-noinfo

Vendor: Rockwellautomation
Product: Micrologix 1400 b firmware 
Version: 21.2;

CVSS2 => (AV:N/AC:L/Au:N/C:P/I:P/A:P)

CVSS Base Score
Impact Subscore
Exploitability Subscore
7.5/10
6.4/10
10/10
Exploit range
Attack complexity
Authentication
Remote
Low
No required
Confidentiality impact
Integrity impact
Availability impact
Partial
Partial
Partial

 References:
https://www.talosintelligence.com/vulnerability_reports/TALOS-2017-0443

Related CVE
CVE-2019-13527
In Rockwell Automation Arena Simulation Software Cat. 9502-Ax, Versions 16.00.00 and earlier, a maliciously crafted Arena file opened by an unsuspecting user may result in the use of a pointer that has not been initialized.
CVE-2019-13511
Rockwell Automation Arena Simulation Software versions 16.00.00 and earlier contain an INFORMATION EXPOSURE CWE-200. A maliciously crafted Arena file opened by an unsuspecting user may result in the limited exposure of information related to the targ...
CVE-2019-13510
Rockwell Automation Arena Simulation Software versions 16.00.00 and earlier contain a USE AFTER FREE CWE-416. A maliciously crafted Arena file opened by an unsuspecting user may result in the application crashing or the execution of arbitrary code.
CVE-2019-10955
In Rockwell Automation MicroLogix 1400 Controllers Series A, All Versions Series B, v15.002 and earlier, MicroLogix 1100 Controllers v14.00 and earlier, CompactLogix 5370 L1 controllers v30.014 and earlier, CompactLogix 5370 L2 controllers v30.014 an...
CVE-2018-19282
Rockwell Automation PowerFlex 525 AC Drives 5.001 and earlier allow remote attackers to cause a denial of service by crashing the Common Industrial Protocol (CIP) network stack. The vulnerability allows the attacker to crash the CIP in a way that it ...
CVE-2019-6553
A vulnerability was found in Rockwell Automation RSLinx Classic versions 4.10.00 and prior. An input validation issue in a .dll file of RSLinx Classic where the data in a Forward Open service request is passed to a fixed size buffer, allowing an atta...
CVE-2018-19016
Rockwell Automation EtherNet/IP Web Server Modules 1756-EWEB (includes 1756-EWEBK) Version 5.001 and earlier, and CompactLogix 1768-EWEB Version 2.005 and earlier. A remote attacker could send a crafted UDP packet to the SNMP service causing a denial...
CVE-2013-2805
Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it receives a datagram with an incorrect...