Vulnerability CVE-2018-11454


Published: 2018-08-07

Description:
A vulnerability has been identified in SIMATIC STEP 7 (TIA Portal) and WinCC (TIA Portal) V10, V11, V12 (All versions), SIMATIC STEP 7 (TIA Portal) and WinCC (TIA Portal) V13 (All versions < V13 SP2 Update 2), SIMATIC STEP 7 (TIA Portal) and WinCC (TIA Portal) V14 (All versions < V14 SP1 Update 6), SIMATIC STEP 7 (TIA Portal) and WinCC (TIA Portal) V15 (All versions < V15 Update 2). Improper file permissions in the default installation of TIA Portal may allow an attacker with local file system access to manipulate resources which may be transferred to devices and executed there by a different user. No special privileges are required, but the victim needs to transfer the manipulated files to a device. Execution is caused on the target device rather than on the PG device.

Type:

CWE-732

CVSS2 => (AV:L/AC:M/Au:N/C:P/I:P/A:P)

CVSS Base Score
Impact Subscore
Exploitability Subscore
4.4/10
6.4/10
3.4/10
Exploit range
Attack complexity
Authentication
Local
Medium
No required
Confidentiality impact
Integrity impact
Availability impact
Partial
Partial
Partial
Affected software
Siemens -> Simatic step 7 (tia portal) 
Siemens -> Simatic wincc (tia portal) 

 References:
http://www.securityfocus.com/bid/105115
https://cert-portal.siemens.com/productcert/pdf/ssa-979106.pdf

Copyright 2024, cxsecurity.com

 