Vulnerability CVE-2018-13798


Published: 2019-03-21

Description:
A vulnerability has been identified in SICAM A8000 CP-8000 (All versions < V14), SICAM A8000 CP-802X (All versions < V14), SICAM A8000 CP-8050 (All versions < V2.00). Specially crafted network packets sent to port 80/TCP or 443/TCP could allow an unauthenticated remote attacker to cause a Denial-of-Service condition of the web server. The security vulnerability could be exploited by an attacker with network access to the affected systems on port 80/TCP or 443/TCP. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the web server. A system reboot is required to recover the web service of the device. At the time of advisory update, exploit code for this security vulnerability is public.

See advisories in our WLB2 database:
Topic
Author
Date
Med.
Siemens SICAM A8000 Series Denial Of Service
Nicolas Heiniger
22.01.2019

Type:

CWE-20

(Improper Input Validation)

CVSS2 => (AV:N/AC:L/Au:N/C:N/I:N/A:C)

CVSS Base Score
Impact Subscore
Exploitability Subscore
7.8/10
6.9/10
10/10
Exploit range
Attack complexity
Authentication
Remote
Low
No required
Confidentiality impact
Integrity impact
Availability impact
None
None
Complete

 References:
https://cert-portal.siemens.com/productcert/pdf/ssa-579309.pdf