A vulnerability has been identified in SIMATIC S7-400 (incl. F) V6 and below (All versions), SIMATIC S7-400 PN/DP V7 (incl. F) (All versions), SIMATIC S7-400H V4.5 and below (All versions), SIMATIC S7-400H V6 (All versions < V6.0.9), SIMATIC S7-410 (All versions < V8.2.1). Specially crafted packets sent to port 102/tcp via Ethernet interface, via PROFIBUS, or via Multi Point Interfaces (MPI) could cause the affected devices to go into defect mode. Manual reboot is required to resume normal operation. Successful exploitation requires an attacker to be able to send specially crafted packets to port 102/tcp via Ethernet interface, via PROFIBUS or Multi Point Interfaces (MPI). No user interaction and no user privileges are required to exploit the security vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the core functionality of the CPU, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known.

Type:

CWE-20

(Improper Input Validation)

CVSS2 => (AV:N/AC:L/Au:N/C:N/I:N/A:C)

CVSS Base Score
Impact Subscore
Exploitability Subscore
7.8/10
6.9/10
10/10
Exploit range
Attack complexity
Authentication
Remote
Low
No required
Confidentiality impact
Integrity impact
Availability impact
None
None
Complete
Affected software
Siemens -> Simatic s7-400 firmware 
Siemens -> Simatic s7-400 pn/dp v7 firmware 
Siemens -> Simatic s7-400h firmware 
Siemens -> Simatic s7-400h v6 firmware 

 References:
https://cert-portal.siemens.com/productcert/pdf/ssa-113131.pdf
https://ics-cert.us-cert.gov/advisories/ICSA-18-317-02