Vulnerability CVE-2018-16557


Published: 2018-12-13

Description:
A vulnerability has been identified in SIMATIC S7-400 (incl. F) V6 and below (All versions), SIMATIC S7-400 PN/DP V7 (incl. F) (All versions), SIMATIC S7-400H V4.5 and below (All versions), SIMATIC S7-400H V6 (All versions < V6.0.9), SIMATIC S7-410 (All versions < V8.2.1). Sending of specially crafted packets to port 102/tcp via Ethernet interface via PROFIBUS or Multi Point Interfaces (MPI) could cause a Denial-of-Service condition on affected devices. Flashing with a firmware image may be required to recover the CPU. Successful exploitation requires an attacker to have network access to port 102/tcp via Ethernet interface or to be able to send messages via PROFIBUS or Multi Point Interfaces (MPI) to the device. No user interaction is required. If no access protection is configured, no privileges are required to exploit the security vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the core functionality of the CPU, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known.

Type:

CWE-20

(Improper Input Validation)

Vendor: Siemens
Product: Simatic s7-400 firmware 
Version: v6.0;
Product: Simatic s7-400h firmware 
Version: v4.5;
Product: Simatic s7-400 pn/dp v7 firmware 
Product: Simatic s7-400h v6 firmware 

CVSS2 => (AV:N/AC:L/Au:N/C:N/I:N/A:C)

CVSS Base Score
Impact Subscore
Exploitability Subscore
7.8/10
6.9/10
10/10
Exploit range
Attack complexity
Authentication
Remote
Low
No required
Confidentiality impact
Integrity impact
Availability impact
None
None
Complete

 References:
https://cert-portal.siemens.com/productcert/pdf/ssa-113131.pdf
https://ics-cert.us-cert.gov/advisories/ICSA-18-317-02

Related CVE
CVE-2019-6584
A vulnerability has been identified in SIEMENS LOGO!8 (6ED1052-xyyxx-0BA8 FS:01 to FS:06 / Firmware version V1.80.xx and V1.81.xx), SIEMENS LOGO!8 (6ED1052-xyy08-0BA0 FS:01 / Firmware version < V1.82.02). The integrated webserver does not invalidate ...
CVE-2019-6571
A vulnerability has been identified in SIEMENS LOGO!8 (6ED1052-xyyxx-0BA8 FS:01 to FS:06 / Firmware version V1.80.xx and V1.81.xx), SIEMENS LOGO!8 (6ED1052-xyy08-0BA0 FS:01 / Firmware version < V1.82.02). An attacker with network access to port 10005...
CVE-2019-6567
A vulnerability has been identified in SCALANCE X-200 (All Versions < V5.2.4), SCALANCE X-200IRT (All versions), SCALANCE X-300 (All versions), SCALANCE X-414-3E (All versions). The affected devices store passwords in a recoverable format. An attacke...
CVE-2019-10926
A vulnerability has been identified in SIMATIC Ident MV420 family (All versions), SIMATIC Ident MV440 family (All versions). Communication with the device is not encrypted. Data transmitted between the device and the user can be obtained by an attack...
CVE-2019-10925
A vulnerability has been identified in SIMATIC Ident MV420 family (All versions), SIMATIC Ident MV440 family (All versions). An authenticated attacker could escalate privileges by sending specially crafted requests to the integrated webserver. The se...
CVE-2019-6578
A vulnerability has been identified in SINAMICS PERFECT HARMONY GH180 with NXG I control, MLFBs: 6SR2...-, 6SR3...-, 6SR4...- (All Versions with option G28), SINAMICS PERFECT HARMONY GH180 with NXG II control, MLFBs: 6SR2...-, 6SR3...-, 6SR4...- (All...
CVE-2019-6577
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15.1 Update 1), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15.1 Update 1), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 un...
CVE-2019-6576
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15.1 Update 1), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15.1 Update 1), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 un...

Copyright 2019, cxsecurity.com

 