Vulnerability CVE-2018-7246


Published: 2018-04-18

Description:
A cleartext transmission of sensitive information vulnerability exists in Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. he integrated web server (Port 80/443/TCP) of the affected devices could allow remote attackers to discover an administrative account. If default on device, it is not using a SSL in settings and if multiple request of the page "Access Control" (IP-address device/ups/pas_cont.htm) account data will be sent in cleartext

Type:

CWE-255

(Credentials Management)

Vendor: Schneider-electric
Product: 66074 mge network management card transverse 

CVSS2 => (AV:N/AC:L/Au:N/C:P/I:N/A:N)

CVSS Base Score
Impact Subscore
Exploitability Subscore
5/10
2.9/10
10/10
Exploit range
Attack complexity
Authentication
Remote
Low
No required
Confidentiality impact
Integrity impact
Availability impact
Partial
None
None

 References:
https://www.schneider-electric.com/en/download/document/SEVD-2018-074-01/

Related CVE
CVE-2018-7762
A vulnerability exists in the web services to process SOAP requests in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow result in a buffer overflow.
CVE-2018-7761
A vulnerability exists in the HTTP request parser in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow arbitrary code execution.
CVE-2018-7760
An authorization bypass vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. Requests to CGI functions allow malicious users to bypass authorization.
CVE-2018-7759
A buffer overflow vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. The buffer overflow vulnerability is caused by the length of the source string specified (instead of the buffer size) as th...
CVE-2018-7758
A denial of service vulnerability exists in Schneider Electric's MiCOM Px4x (P540 range excluded) with legacy Ethernet board, MiCOM P540D Range with Legacy Ethernet Board, and MiCOM Px4x Rejuvenated could lose network communication in case of TCP/IP ...
CVE-2018-7245
An improper authorization vulnerability exists In Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. The integrated web server (Port 80/443/TCP) of the affected devices could allow a remote attacker to...
CVE-2018-7244
An information disclosure vulnerability exists In Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. The integrated web server (Port 80/443/TCP) of the affected devices could allow a remote attacker to...
CVE-2018-7243
An authorization bypass vulnerability exists In Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. The integrated web server (Port 80/443/TCP) of the affected devices could allow a remote attacker to g...