Vulnerability CVE-2019-10943


Published: 2019-08-13

Description:
A vulnerability has been identified in SIMATIC ET 200SP Open Controller CPU 1515SP PC (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (All versions), SIMATIC S7-1200 CPU family (All versions >= V4.0), SIMATIC S7-1500 CPU family (All versions), SIMATIC S7-1500 Software Controller (All versions), SIMATIC S7-PLCSIM Advanced (All versions). An attacker with network access to port 102/tcp could potentially modify the user program on the PLC in a way that the running code is different from the source code which is stored on the device. An attacker must have network access to affected devices and must be able to perform changes to the user program. The vulnerability could impact the perceived integrity of the user program stored on the CPU. An engineer that tries to obtain the code of the user program running on the device, can receive different source code that is not actually running on the device. No public exploitation of the vulnerability was known at the time of advisory publication.

Type:

CWE-284

(Improper Access Control)

Vendor: Siemens
Product: Simatic s7-1200 cpu 1212c firmware 
Version: 4.0;
Product: Simatic s7-1200 cpu 1215c firmware 
Version: 4.0;
Product: Simatic s7-1200 cpu 1211c firmware 
Version: 4.0;
Product: Simatic s7-1200 cpu 1214c firmware 
Version: 4.0;
Product: Simatic s7-1200 cpu 1217c firmware 
Version: 4.0;
Product: Simatic s7-1500 
Product: Simatic et 200sp open controller cpu 1515sp pc2 firmware 
Product: Simatic s7-1500 cpu 1511c firmware 
Product: Simatic s7-1500 cpu 1518 firmware 
Product: Simatic s7-plcsim advanced 
Product: Simatic et 200sp open controller cpu 1515sp pc firmware 
Product: Simatic s7-1500 cpu 1512c firmware 

CVSS2 => (AV:N/AC:L/Au:N/C:N/I:P/A:N)

CVSS Base Score
Impact Subscore
Exploitability Subscore
5/10
2.9/10
10/10
Exploit range
Attack complexity
Authentication
Remote
Low
No required
Confidentiality impact
Integrity impact
Availability impact
None
Partial
None

 References:
https://cert-portal.siemens.com/productcert/pdf/ssa-232418.pdf

Related CVE
CVE-2019-10942
A vulnerability has been identified in SCALANCE X-200 (All versions), SCALANCE X-200IRT (All versions), SCALANCE X-200RNA (All versions). The device contains a vulnerability that could allow an attacker to trigger a denial-of-service condition by sen...
CVE-2019-10929
A vulnerability has been identified in SIMATIC ET 200SP Open Controller CPU 1515SP PC (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (All versions), SIMATIC S7-1200 CPU family (All versions >= V4.0), SIMATIC S7-1500 CPU family (All v...
CVE-2019-10928
A vulnerability has been identified in SCALANCE SC-600 (V2.0). An authenticated attacker with access to port 22/tcp as well as physical access to an affected device may trigger the device to allow execution of arbitrary commands. The security vulnera...
CVE-2019-10927
A vulnerability has been identified in SCALANCE SC-600 (V2.0), SCALANCE XB-200 (V4.1), SCALANCE XC-200 (V4.1), SCALANCE XF-200BA (V4.1), SCALANCE XP-200 (V4.1), SCALANCE XR-300WG (V4.1). An authenticated attacker with network access to to port 22/tcp...
CVE-2019-12261
Wind River VxWorks 6.7 though 6.9 and vx7 has a Buffer Overflow in the TCP component (issue 3 of 4). This is an IPNET security vulnerability: TCP Urgent Pointer state confusion during connect() to a remote host.
CVE-2019-12260
Wind River VxWorks 6.9 and vx7 has a Buffer Overflow in the TCP component (issue 2 of 4). This is an IPNET security vulnerability: TCP Urgent Pointer state confusion caused by a malformed TCP AO option.
CVE-2019-12258
Wind River VxWorks 6.6 through vx7 has Session Fixation in the TCP component. This is a IPNET security vulnerability: DoS of TCP connection via malformed TCP options.
CVE-2019-12255
Wind River VxWorks 6.6 through 6.9 has a Buffer Overflow in the TCP component (issue 1 of 4). This is a IPNET security vulnerability: TCP Urgent Pointer = 0 that leads to an integer underflow.

Copyright 2019, cxsecurity.com

 

Back to Top