Vulnerability CVE-2019-19279


Published: 2020-03-10

Description:
A vulnerability has been identified in SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules (All versions). Specially crafted packets sent to port 50000/UDP of the EN100 Ethernet communication modules could cause a Denial-of-Service of the affected device. A manual reboot is required to recover the service of the device. At the time of advisory publication no public exploitation of this security vulnerability was known to Siemens.

Type:

CWE-20

(Improper Input Validation)

CVSS2 => (AV:N/AC:L/Au:N/C:N/I:N/A:C)

CVSS Base Score
Impact Subscore
Exploitability Subscore
7.8/10
6.9/10
10/10
Exploit range
Attack complexity
Authentication
Remote
Low
No required
Confidentiality impact
Integrity impact
Availability impact
None
None
Complete
Affected software
Siemens -> Siprotec 4 
Siemens -> Siprotec compact 

 References:
https://cert-portal.siemens.com/productcert/pdf/ssa-974843.pdf