Vulnerability CVE-2020-5806


Published: 2020-12-29

Description:
An attacker-controlled memory allocation size can be passed to the C++ new operator in the CServerManager::HandleBrowseLoadIconStreamRequest in messaging.dll. This can be done by sending a specially crafted message to 127.0.0.1:7153. Observed in FactoryTalk Linx 6.11. All versions of FactoryTalk Linx are affected.

Type:

CWE-770

CVSS2 => (AV:L/AC:L/Au:N/C:N/I:N/A:P)

CVSS Base Score
Impact Subscore
Exploitability Subscore
2.1/10
2.9/10
3.9/10
Exploit range
Attack complexity
Authentication
Local
Low
No required
Confidentiality impact
Integrity impact
Availability impact
None
None
Partial
Affected software
Rockwellautomation -> Factorytalk linx 

 References:
https://www.tenable.com/security/research/tra-2020-71