Vulnerability CVE-2021-31884


Published: 2021-11-09

Description:
A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions), APOGEE PXC Compact (P2 Ethernet) (All versions), APOGEE PXC Modular (BACnet) (All versions), APOGEE PXC Modular (P2 Ethernet) (All versions), Capital VSTAR (All versions), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus Source Code (All versions), TALON TC Compact (BACnet) (All versions), TALON TC Modular (BACnet) (All versions). The DHCP client application assumes that the data supplied with the ??Hostname? DHCP option is NULL terminated. In cases when global hostname variable is not defined, this may lead to Out-of-bound reads, writes, and Denial-of-service conditions. (FSMD-2021-0014)

Type:

CWE-125

(Out-of-bounds Read)

CVSS2 => (AV:N/AC:L/Au:N/C:P/I:P/A:P)

CVSS Base Score
Impact Subscore
Exploitability Subscore
7.5/10
6.4/10
10/10
Exploit range
Attack complexity
Authentication
Remote
Low
No required
Confidentiality impact
Integrity impact
Availability impact
Partial
Partial
Partial
Affected software
Siemens -> Capital vstar 
Siemens -> Nucleus net 
Siemens -> Nucleus readystart v3 
Siemens -> Nucleus readystart v4 
Siemens -> Nucleus source code 

 References:
https://cert-portal.siemens.com/productcert/pdf/ssa-044112.pdf
https://cert-portal.siemens.com/productcert/pdf/ssa-114589.pdf

Copyright 2024, cxsecurity.com

 