Vulnerability CVE-2021-35533


Published: 2021-11-26

Description:
Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).

Type:

CWE-20

(Improper Input Validation)

CVSS2 => (AV:N/AC:M/Au:N/C:N/I:N/A:C)

CVSS Base Score
Impact Subscore
Exploitability Subscore
7.1/10
6.9/10
8.6/10
Exploit range
Attack complexity
Authentication
Remote
Medium
No required
Confidentiality impact
Integrity impact
Availability impact
None
None
Complete

 References:
https://search.abb.com/library/Download.aspx?DocumentID=8DBD000063&LanguageCode=en&DocumentPartId=&Action=Launch

Copyright 2024, cxsecurity.com

 