Vulnerability CVE-2017-6015
Published: 2018-05-11
Description: |
Without quotation marks, any whitespace in the file path for Rockwell Automation FactoryTalk Activation version 4.00.02 remains ambiguous, which may allow an attacker to link to or run a malicious executable. This may allow an authorized, but not privileged local user to execute arbitrary code with elevated privileges on the system. CVSS v3 base score: 8.8, CVSS vector string: (AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H). Rockwell Automation has released a new version of FactoryTalk Activation, Version 4.01, which addresses the identified vulnerability. Rockwell Automation recommends upgrading to the latest version of FactoryTalk Activation, Version 4.01 or later. |
Type:
CWE-74
CVSS2 => (AV:L/AC:L/Au:N/C:C/I:C/A:C)
CVSS Base Score |
Impact Subscore |
Exploitability Subscore |
7.2/10 |
10/10 |
3.9/10 |
Exploit range |
Attack complexity |
Authentication |
Local |
Low |
No required |
Confidentiality impact |
Integrity impact |
Availability impact |
Complete |
Complete |
Complete |
References: |
http://www.securityfocus.com/bid/96996
https://ics-cert.us-cert.gov/advisories/ICSA-17-047-02
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/939382
|
|
|