Vulnerability CVE-2022-33139


Published: 2022-06-21

Description:
A vulnerability has been identified in SIMATIC WinCC OA V3.16 (All versions in default configuration), SIMATIC WinCC OA V3.17 (All versions in non-default configuration), SIMATIC WinCC OA V3.18 (All versions in non-default configuration). Affected applications use client-side only authentication, when neither server-side authentication (SSA) nor Kerberos authentication is enabled. In this configuration, attackers could impersonate other users or exploit the client-server protocol without being authenticated.

Type:

CWE-287

(Improper Authentication)

CVSS2 => (AV:N/AC:M/Au:N/C:P/I:P/A:P)

CVSS Base Score
Impact Subscore
Exploitability Subscore
6.8/10
6.4/10
8.6/10
Exploit range
Attack complexity
Authentication
Remote
Medium
No required
Confidentiality impact
Integrity impact
Availability impact
Partial
Partial
Partial
Affected software
Siemens -> Wincc open architecture 